APC
APC MGE Galaxy 5500 120kVA 400-415V Single UPS Off Shore IP22 RAL 7035, Start-up 5X8 – G55TUPU120HXS
Part No: G55TUPU120HXS
AED 578$157 USD
Authorized B2B supply from DISTI Middle East (UAE & MENA). Genuine stock, project pricing, and fast regional dispatch.
Request a QuoteSpecifications
- Manufacturer
- APC
- Model
- APC G55TUPU120HXS
- Manufacturer Part No
- G55TUPU120HXS
Alternate / cross-brand similar products
AI-matched alternatives based on specifications

UNV
UNV UPS800-SEA-UK 800VA/480W Uninterrupted Power Supply British Standard Socket Version
AED 194

EATON
Eaton 93T40KMBSB 93T UPS 40 kVA, 3 phase in 3 phase out Tower Online UPS
AED 11,051

VERTIV
Vertiv GXTRT-3000IRT2UXL UPS 3kVA 230V
AED 3,360

MARSRIVA
Marsriva MR-US6KRT-H 6kVA 192V, 1:1 phase, W/O battery, rack mount Smart Online UPS
AED 105

VERTIV
Vertiv GXTRT-2000IRT2UXL UPS 2kVA 230V
AED 3,675

Hikvision
HikVision DS-UPS3000 3000VA/1800W Uninterruptible Power Supply UPS CCTV
AED 683

Hikvision
HikVision DS-UPS2000 2000VA 1200W Uninterruptible Power Supply UPS CCTV
AED 420

MARSRIVA
Marsriva MR-US10KRT-H 10KVA 192V, 1:1 phase, W/O battery, rack mount Smart Online UPS
AED 2,671
Product description & technical overview
APC APC G55TUPU120HXS
Tech Specification
Output
Output power capacity
108.0 KWatts / 120.0 kVA
Max Configurable Power (Watts)
108.0 KWatts / 120.0 kVA
Nominal Output Voltage
400V 3PH
Neutral Output Current
260A
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Efficiency at Full Load
93.0 %
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
50 Hz – programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8%
Output Frequency (not synced)
50Hz +/- 0.1% for 50Hz nominal
Other Output Voltages
380, 415
Load Crest Factor
3 : 1
Topology
Double Conversion Online
Waveform type
Sine wave
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
Maximum Output Current
480
Output Voltage THD
< 1% linear load and < 2.5% nonlinear load
Output Voltage Tolerance
+/- 2% static and 100% load step
Bypass
Built-in Maintenance Bypass, Built-in Static Bypass, Optional External Bypass
Input
Nominal Input Voltage
400V 3PH
Input frequency
45 – 65 Hz
Input Connections
Hard Wire 4-wire (3PH + G), Hard Wire 4-wire (3PH + N)
Input voltage range for main operations
323 – 437 (380V), 340 – 460 (400V), 353 – 477 (415V)V
Efficiency at Full Load
93.0 %
Input Total Harmonic Distortion
Less than 3% for full load
Type of Input Protection Required
gL fuse
Other Input Voltages
380, 415
Maximum Short Circuit Withstand (Icw)
30.0kAmps
Maximum Input Current
228.0A
Input Power Factor at Full Load
1.0
Batteries & Runtime
Battery type
No internal battery – uses external battery system
Expected Battery Life (years)
8 – 10
Runtime
View Runtime Graph
View Runtime Chart
Communications & Management
Pre-Installed SmartSlot Cards
AP9635CH
Control panel
Multi-function LCD status and control console
Emergency Power Off (EPO)
Yes
Available SmartSlot Interface Quantity
3
Physical
Maximum Height
2180mm , 218.0CM
Maximum Width
712mm , 71.2CM
Maximum Depth
855mm , 85.5CM
Net Weight
556.0KG
Shipping weight
610.0KG
Shipping Height
2300mm , 230.0CM
Shipping Width
1080mm , 108.0CM
Shipping Depth
1200mm , 120.0CM
Units per Pallet
1.0
Environmental
Operating Temperature
0 – 40 C
Operating Relative Humidity
0 – 95 %
Operating Elevation
0-999,9meters
Storage Temperature
-20 – 45 C
Storage Relative Humidity
0 – 95 %
Storage Elevation
0-12000meters
Audible noise at 1 meter from surface of unit
63.0dBA
Protection Class
IP 32, IP20